Quick Links
 
 
 
 
 

VAC Training

Interested in joining us for our next training class? Click HERE for more information!

 
 
 

Like us on Facebook
 
 
 

Digital Training Class

Graduates

 
 
 
 
We are proud to announce the graduates of our very first digital focused training class. Pictured left to right: Steve Hendricks from SDH Flow Controls, JC Labelle from Belletek Controls, Dic Gabriel from Wolseley Industrial Group (Mobile), Bob Kelly from DAK Americas, Thomas Griffing from DAK Americas, and Nate Worzalla from Star Marketing. 

Thank you to everyone who attended. We enjoyed having you, and hope you walked away from our class feeling more knowledgeable about our product line. 

Our training classes are a great opportunity to learn more about our products while getting hands on experience in our shop. Contact Brenna Locklear to register for our next available class, or click HERE for more information about what to expect during training.
 
 
 
 
TECH TIP: Fail Last, Fail In Place, Fail Freeze
 
 
 
 
 
 
There are many industrial control valve applications that require the valve to stay at the last set point as a failure state. This is frequently called out as Fail Last Position, Fail in Place, or Fail Freeze. These terms are interchangeable, so we will use Fail Freeze for the rest of this article.

When specifying a positioner for these applications it is important to understand that with a positioner there are two separate failure modes.

1. Loss of Signal is when the signal that provides the set point from the control system is interrupted.
2. Loss of Air Supply is when the instrument air supply that provides the motive power for the pneumatic actuator is interrupted.

These must be treated as independent conditions. With Fail Freeze it is imperative that you understand which failure mode the end user needs. Is the application “Fail Freeze on Loss of Signal”, “Loss of Air Supply”, or both? The answer will let you specify the correct positioner and/or accessories.

Fail Freeze on loss of Signal:
This is accomplished using a positioner configured with an I/P module specifically designed to hold the air pressure in the actuator when the voltage of the signal drops below the minimum required to operate the I/P. This is typically in the range of 9-12 VDC. When the signal is lost, the valve will be held at or near the set point and will not drift. When the signal is restored, the positioner will resume normal operation without operator intervention.
Fail Freeze Positioners or I/P’s cannot be converted from Fail Freeze to Fail Safe or vice versa. You must purchase the correct positioner for your application.
 
 
 
 
Fail Freeze on loss of Air Supply:
This is a less well understood failure condition. It is commonly thought that using a double acting actuator will accomplish this. While this may work with an On/Off application, control valves using a positioner operate differently. Loss of air can occur in two different ways.
1.    Sudden air loss: Air pressure can fail suddenly such as the instrument airline is broken close to the control valve and air is exhausted from the positioner/actuator combination quickly. In this failure mode the valve MAY stay at the set point or close to it. Process forces, valve & actuator type, and the speed of air loss will greatly affect the actual valve position after loss of signal. It is possible for the valve position to drift under these conditions.
2.    Slow air loss: Air pressure that fails slowly such as a compressor trip, will cause the valve to drift as air pressure slowly drops and the actuator doesn’t have the power to hold the valve in place. The pressure on both sides of the actuator is no longer balanced and the valve will be forced to close because the positioner can’t maintain the pressure balance. The valve will absolutely drift under this condition.

The only way to reliably provide Fail Freeze on loss of air supply is accomplished using a pneumatic lockup valve between the positioner and actuator. This valve has a sensing port that is connected to the instrument air supply a short distance from the valve. There is also an adjustable set point. By adjusting the set point to approximately 10% below the supply pressure, the lock up valve will shift to hold the air in the actuator when the supply pressure falls below the set point. After the valve has locked up the valve will not drift.
When air pressure is restored the lock up valve will shift automatically to restore air supply to the actuator. No operator intervention is needed.
 
 
 
 
 
 
 
 
Click here to watch our
D400 Fail Freeze video.
 
 
 
 
 
 
 
 
 


We have a good stock of digital  products on our shelves right now.

In most cases, we can process and ship orders within 48 hours
 
 
 
 
 
We will be closed on March 30 in observation of Good Friday. We hope you have a happy and blessed Easter!
 
 
 
 
Thank you for your continued support of our product line. If you have any questions or would like to receive product brochures, please call us or visit our website for additional information. Click HERE to be redirected. 

Sincerely,
Randy Estes
Valve Accessories & Controls 
 
 
 
 

200 Jade Park, Alabama, USA |  205·678·0507

 
 
Footer-logo